4.1.2 MAX15500 Output Conditioners
Following USB connection, the MAX15500 Output Conditioners section will refresh to show the default
configuration and initial error states of the MAX1550 devices. Upon any power-up (or supply brownout
condition), the Supply Brownout alarm is expected. A red LED on the MAXREFDES24 hardware will also be
on. A subsequent Refresh of the MAX15500 Output Conditioners section will clear the alarm.
One can set the Brownout threshold in 2V increments from ±10V to ±24V. In the MAXREFDES24 design, a
brownout threshold of ±24V triggers a Supply Brownout alarm.
The default mode upon power up for the analog outputs is Standby with a ±10V brownout threshold and
thermal protection disabled. Use the Configuration sections to configure the on-board MAX15500 signal
conditioners to output common industrial control signal ranges (current or voltage) and to read back any error
conditions the MAX15500 report.
Use the Refresh button to read and refresh the Configuration and Error(s) status of the MAX15500
devices.
Use the Apply button to write the displayed configuration to the MAX15500 devices. Enable Refresh
On Apply to immediately issue a read or Refresh command following a write or Apply.