MAX15303 PMBus Command Set User’s Guide
Page 13 of 52
VOUT_DROOP
accurate adaptive voltage positioning results with the VOUT_DROOP command.
Note tha
t VOUT_DROOP can accept negative resistance values, allowing a user to compensation for
resistive losses between the output voltage remote sense point and the load, if desired. (Setting
VOUT_DROOP to a negative value will case output voltage to rise with increasing load.)
Wait at least 500μs for execution after sending the VOUT_DROOP command before sending
additional PMBus commands.